GET SUVTP20KH4B4S APC Smart-UPS VT 20kVA 400V at the best price in Kenya from Starmac Technologies.
SUVTP20KH4B4S APC Smart-UPS VT 20kVA 400V w/4 Batt. Mod., Start-Up 5X8, Internal Maint Bypass, Parallel Capability with AP9631 Preinstalled. 6 .0 kWatts Confirgurable Power , Double Conversion Online , Pure sinewave , Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage ,304 – 477V Input Voltage , 400V 3PH Hard Wire 5-wire (3PH + N + G) Included Battery Modules 4 = 9810 VAH , DB-9 RS-232, Smart-Slot Multi-function LCD status and control console,DB-9 RS-232, Smart-Slot
Max. Capacity Used
100%
Output power capacity
16.0kWatts / 20.0kVA
Nominal Output Voltage
400V 3PH
Nominal Input Voltage
400V 3PH
Input Connections
Hard Wire 5-wire (3PH + N + G)
Maximum Input Current
27.0A
APC Smart-UPS VT 20kVA 400V w/4 Batt. Mod., Start-Up 5X8, Internal Maint Bypass, Parallel Capability
Effective 10-40kVA 3 phase UPS power protection against downtime and data loss for mission critical applications.
Includes: Battery modules ship installed, Bolt Down Brackets, CD with software, Installation Guide, Network Management Card, Power modules ship installed, Start up included, User Manual
- Parallel-capacity capable
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
- Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
Smart-UPS VT Features & Benefits
Marketing Features
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Total Cost of Ownership
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Manual maintenance bypass
Reduces installation costs by eliminating the need for an external mechanical bypass.
Serviceability
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Shippable with modules installed
Enables pre-installation UPS staging and testing and faster installation.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Battery replacement without tools
Enables fast battery replacement, lowering Mean Time to Repair (MTTR).
Protection
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Cold-start capable
Provides temporary battery power when the utility power is out.
Manageability
SmartSlot
Customize UPS capabilities with management cards.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure Manager.
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Audible alarms
Provides notification of changing utility power and UPS power conditions
Programmable frequency
Ensures compatibility with different input frequencies.
Network manageable
Provides remote power management of the UPS over the network.
LED status indicators
Quickly understand unit and power status with visual indicators.
Sustainability
EU CoC for UPS
Ensures that UPSs sold in the EU are highly efficient
Availability
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Scalable runtime
Allows additional run time to be quickly added as needed.
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.
OUTPUT POWER CAPACITY |
16.0 KW / 20.0 kVA
|
|
---|---|---|
MAX CONFIGURABLE POWER (WATTS) |
16.0 KW / 20.0 kVA
|
|
NOMINAL OUTPUT VOLTAGE |
400 3PH
|
|
OUTPUT VOLTAGE NOTE |
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
|
|
OUTPUT VOLTAGE DISTORTION |
Less than 5% at full load
|
|
OUTPUT FREQUENCY (SYNC TO MAINS) |
47 – 53 Hz for 50 Hz nominal
|
|
OTHER OUTPUT VOLTAGES |
380, 415V
|
|
CREST FACTOR |
3 : 1
|
|
Double Conversion Online
|
||
WAVEFORM TYPE |
Sine wave
|
|
OUTPUT CONNECTIONS |
(1) Hard Wire 4-wire (3PH + G) (Battery Backup) , (1) Hard Wire 5-wire (3PH + N + G) (Battery Backup) , (1) Screw Terminals (Battery Backup)
|
|
BYPASS |
Built-in Maintenance Bypass , Built-in Static Bypass
|
NOMINAL INPUT VOLTAGE |
400 3PH
|
|
---|---|---|
INPUT FREQUENCY |
40 – 70 Hz (auto sensing)
|
|
INPUT CONNECTIONS |
Hard Wire 5-wire (3PH + N + G)
|
|
INPUT VOLTAGE RANGE FOR MAIN OPERATIONS |
304 – 477 V
|
|
OTHER INPUT VOLTAGES |
380 , 415
|
|
MAXIMUM INPUT CURRENT |
27 A
|
|
INPUT BREAKER CAPACITY |
50 A
|
BATTERY TYPE |
VRLA
|
|
---|---|---|
INCLUDED BATTERY MODULES |
4
|
|
TYPICAL RECHARGE TIME |
5 hour(s)
|
|
RBC QUANTITY |
4
|
|
NOMINAL BATTERY VOLTAGE |
+/-192 V (split battery referenced to neutral)
|
|
END OF DISCHARGE BATTERY VOLTAGE |
+/-154 V
|
INTERFACE PORT(S) |
DB-9 RS-232 , Smart-Slot
|
|
---|---|---|
PRE-INSTALLED SMARTSLOT™ CARDS |
AP9631
|
|
CONTROL PANEL |
Multi-function LCD status and control console
|
|
AUDIBLE ALARM |
Audible and visible alarms prioritized by severity
|
|
EMERGENCY POWER OFF (EPO) |
Yes
|
MAXIMUM HEIGHT |
1490.0 mm
|
|
---|---|---|
MAXIMUM WIDTH |
523.0 mm
|
|
MAXIMUM DEPTH |
842.0 mm
|
|
NET WEIGHT |
599.09 kg
|
|
SHIPPING WEIGHT |
630.0 kg
|
|
SHIPPING HEIGHT |
1643.0 mm
|
|
SHIPPING WIDTH |
650.0 mm
|
|
SHIPPING DEPTH |
1062.0 mm
|
|
COLOR |
Black
|
|
UNITS PER PALLET |
1.0
|
OPERATING ENVIRONMENT |
0 – 40 °C
|
|
---|---|---|
OPERATING RELATIVE HUMIDITY |
0 – 95 %
|
|
OPERATING ELEVATION |
0-999.9 meters
|
|
STORAGE TEMPERATURE |
-50 – 40 °C
|
|
STORAGE RELATIVE HUMIDITY |
0 – 95 %
|
|
STORAGE ELEVATION |
0-15000 meters
|
|
AUDIBLE NOISE AT 1 METER FROM SURFACE OF UNIT |
51.300 dB
|
|
ONLINE THERMAL DISSIPATION |
3112.000 BTU/hr
|
|
PROTECTION CLASS |
IP 20
|